Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency two way communication phone does not work. Repair or replace and reinspect in 14 days
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No Permanent means of temperature control are inoperable and shall be repaired, or replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Both traveling cables containing wiring to car have cracks and have worn thru in several places to outer layers of insulation, despite previous repairs. Repair or replace same
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) Yes No Need to replace missing hoistway door restrictor angles as needed. Re-inspection required
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Car top shall be kept clean of dust and debris.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a Yes No Clean debris from elevator pit. 1/16/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working. 3/9/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a Yes No Clean pit of all rubbish. 3/9/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 4/7/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency light does not work. 4/7/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two way communication inoperable. Re-inspection required 3/10/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency two way communication phone does not work. Repair or replace and reinspect in 14 days. 3/24/25 9/30/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No The handrail on the left side and rear of the car are lose. Handrails shall be tightened. A17.1 2016 - 5.8.1.10 9/30/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No One of the traveling cables has electrical tape on likely indicating that there is a break in the exterior protective coating. Replace traveling cable. A17.1 2016 - 5.1.7.1 9/30/2025
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No Permanent means of temperature control are inoperable and shall be repaired, or replaced. 9/30/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Car top shall be kept clean of dust and debris. 9/30/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency two way communication phone does not work. Repair or replace and reinspect in 14 days. 9/25/2025 4/14/2026
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No Permanent means of temperature control are inoperable and shall be repaired, or replaced. 4/14/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 4/14/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Car top shall be kept clean of dust and debris. 4/14/2026