MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Inspection incomplete. Must perform all the weight test, counter weight buffer, set safeties, 125% brake test
|
12/19/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
The car door operator was out of service and full inspection on the car door operation could not made. Repair car door operator and a reinspection is required to ensure proper operation.
|
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Means of two way communication are inoperable and shall be repaired or replaced. 2.27.1
|
9/30/2025
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Reprogram emergency phone.
|
4/7/2022
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
1001.2(b)(6)
|
|
|
Repair air conditioning in machine room.
|
9/30/2025
|
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Refasten loose, bottom terminal floor hoistway door sight guard
|
9/30/2025
|
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Refasten loose, bottom terminal floor hoistway door sight guard.
|
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
Permanent means of temperature control are inoperable and shall be repaired, or replaced.
|
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
Permanent means of temperature control are inoperable and shall be repaired, or replaced.
|
9/30/2025
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
Permanent means of temperature control are inoperable and shall be repaired, or replaced.
|
9/30/2025
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean rubbish from pit.
|
9/30/2025
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
Clean debris from elevator pit.
|
1/16/2020
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Clean pit.
|
9/30/2025
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two way communication inoperable. Re-inspection required
|
12/10/2024
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Means of two way communication are inoperable and shall be repaired or replaced.
|
3/11/2025
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
x
|
|
Fireman’s service operation could not be completed due to the car door operator being out of service. Repair door operator to fireman’s service. Reinspection is required.
|
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
x
|
|
Phase 2 call cancel is inoperable and shall be repaired or replaced.
|
3/11/2025
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
|