Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test is incomplete. Complete the step indexing, bottom comb plate testing, missing step sensor, and handrail speed sensor 3/4/2022
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(3) Escalators Placed out of Service x x The escalator has been removed and demolished.
A17.1-1996 : Escalators 7.17 - Step/skirt clearances, panels, and performance index 1008.2s Need to perform step indexing test. 8/1/2019
A17.1-1996 : Escalators 7.5 - Lighting 1009.2d Demarcation lights on top not working. Repair 2/20/2020
A17.1-1996 : Escalators 7.7 - Combplate and comb step impact device 805.3n x The center vertical comb impact device was not triggering until 250 lbf. Unit was RED TAGGED until force is reduced. 3/4/2022
A17.1-1996 : Escalators 7.9 - Steps and upthrust device 1105.1 x Replace broken steps. Unit red tagged. 9/8/2020
conversion conversion n/a Drips and steps need to be cleaned of oil and dirt. 8/1/2019