MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light shall work. It is broken, the car hits the guard.
|
|
A17.1-1996 : Elevators
|
3.29 - Counterweight safeties
|
1001.2(c)(14)
|
x
|
x
|
Counterweight safety is not working. Red tagged elevator.
|
4/13/2021
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Car door restrictor shall work at all floors.
|
5/28/2024
|
A17.1-1996 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
201
|
|
|
Counterweight roller is dragging. Repair or replace.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.8 Switch Keys
|
|
|
Replace mislabeled Phase I fire service key switch.
|
6/1/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP, including PM records and monthly fire service test log, shall be present.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Cartop inspection intermittently does not work.
|
|