Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/1/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 7/1/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Compliant/Required documentation shall be kept in the equipment room (neat/organized) including PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. 8/21/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Emergency lowering is not working. 6/6/2024