MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. The evacuation instructions are missing. (This item is for notification purposes for future violation in 2022)
|
1/15/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car emergency lighting shall be operational.
|
9/19/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
6/9/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
The return hydraulic hose in tank is split and needs replacement.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
x
|
|
Provide proper machine room lighting
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
x
|
|
Patch hole in drywall south wall in machine room
|
|
A17.1-2016 : Elevators
|
1.3 - Operating control devices
|
8.11.2.1.1(c)
|
x
|
|
Number disconnect and controllers
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Service fire extinguisher
|
|