Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated Missouri Operating Certificate in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace phase II bezel so off hold on car key switch can be read
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written copy of the MCP shall be kept in the machine room for each unit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Could not access electrical panel to test emergency lights. Restricted access floor, Need to test emergency lights. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Need to replace phase II key switch bezel. All wording (off, on & hold) are missing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Need to replace worn out and damaged car top guide rollers
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 x Elevator car door reopening device (light ray) does not work. Repair ore replace light ray. Re-inspection required
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Call cancel button on phase II fire service does not work, repair needed. Cannot shut elevator down. Only elevator to move patients from floors 2 and 4. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not work, needs repair. Re-inspection required
conversion conversion n/a Phase II Fire service key bezel needs to be replaced 9/3/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x Door restrictor is not working. 9/3/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Car top light needs to be repaired. 9/3/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase I car panel light not working. 9/3/2019
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Repair call cancel button. Cannot shut elevator off. Only elevator in building that goes to 2 and 4 floors. Reinspect 30 days 6/24/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Call cancel button on Phase 2 fire service does not work, needs repaired. Re-inspection required 5/13/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not work, needs repaired. Re-inspection required 5/13/2025