Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(E) Replaced comb plates with missing teeth. 2/7/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps x x Step has broken riser. 3 steps have broken fin on step treads. Red tagged until repaired. 8/4/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x The step/skirt index is at too great of a gap and coefficient. Adjust step/skirt index to be under the maximum limits.
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing 8.6.11.6.1(b)(Not accessible to public) The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway.
conversion conversion n/a both bottom and top demarcation lights not working 2/7/2020