Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No both bottom and top demarcation lights not working 2/7/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(E) No No Replaced comb plates with missing teeth. 2/7/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps Yes Yes Step has broken riser. 3 steps have broken fin on step treads. Red tagged until repaired. 8/4/2022
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing 8.6.11.6.1(b)(Not accessible to public) No No The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway. 5/8/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records No No There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. 5/8/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance Yes No The step/skirt index is at too great of a gap and coefficient. Adjust step/skirt index to be under the maximum limits. 6/10/2025
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing 8.6.11.6.1(b)(Not accessible to public) No No The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway. 5/8/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records No No There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. 5/8/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance Yes No The step/skirt index is at too great of a gap and coefficient. Adjust step/skirt index to be under the maximum limits. 8/6/2025
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes Yes Step/Skirt index at too great of a gap. Adjust step/skirt index to be under the maximum limit. Unit red tagged. 5/8/2026
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(3) Escalators Placed out of Service Yes Yes The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway. 5/8/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records No No There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. 5/8/2026
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing 8.6.11.6.1(b)(Not accessible to public) No No The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway.
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(3) Escalators Placed out of Service Yes Yes Escalator was Red-tagged on 8/6/25 for a failed step indexing test. Step indexing test was performed and reading were above threshold for safe operation (.4309) Escalator will remain Red-tagged and locked out for service. Re-inspection required.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.11.4.1(e) Lighting (demarcation and step lighting) No No Top and bottom demarcation lights do not work, need repaired
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Clean escalator truss space
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps Yes No Replace step with broken step thread. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unable to perform testing of brake torque and step indexing due to tool failure. Need to perform both tests to complete inspection. Re-inspection required 8/6/2025