Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 8.12 - Steps, step chains, and trusses 8.6.8.15.12 Yes Yes Step chains are stretched and worn out creating excessive gap at top landing (1/4") Replace step chains. Red-tagged, removed from service. Re-inspection required
A17.1-2016 : Elevators 7.9 - Steps and upthrust device 8.6.8.15.9 Yes Yes Lower landing left side upthrust device is broken and will not actuate switch as designed. Red-tagged and removed from service. Re-inspection required
A17.1-2016 : Elevators 7.19 - Maintenance records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No Provide up-to-date wiring diagrams
A17.1-2016 : Elevators 7.17 - Step/skirt clearances, panels, and performance index 8.6.8.3.3 Yes No Need to perform step indexing test. Re-inspection required
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing 8.6.11.6.1(b)(Not accessible to public) No No The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway. 5/7/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Escalator malfunctioned and quit running during test. Need to perform the following tests to complete inspection: test drive machine brake torque, stop switches in machine space, all upthrust devices, test all skirt switches, step chain carriage switches, perform step indexing test & test handrail inlet switches. Re-inspection required 8/7/2025
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing 8.6.11.6.1(b)(Not accessible to public) No No The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records No No There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. 5/7/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records No No Provide maintenance control program and current maintenance records 5/7/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records No No There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. 5/7/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Clean escalator truss and machine space 5/7/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Clean escalator truss and machine space. 5/7/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps Yes No Replace steps witch broken treads. Re-inspection required 5/7/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps Yes No Replace steps witch broken treads. Re-inspection required 8/7/2025
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning No No Clean escalator truss and machine space.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps Yes No Replace steps witch broken treads. Re-inspection required