MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
No audible on Phase I return.
|
9/3/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
|
|
The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to test counterweight buffer at rated speed. Re-inspection required
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A written copy of the MCP shall be kept in the machine room for each unit.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to test elevator for operation on emergency power. Re-inspection required
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(d) On-Site Maintenance Records (Permanent Records)
|
|
|
Current maintenance records shall be kept in the elevator machine room
|
|