Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 No No Bottom floor hoistway door interlock cover is missing, re-install cover 11/21/2025
MO Minimum : Elevators (A) - Hoistways (A)16 No No Bottom floor hoistway door interlock cover is missing, re-install cover 11/21/2025
MO Minimum : Elevators (A) - Hoistways (A)16 No No Bottom floor hoistway door interlock cover is missing, re-install cover 3/25/2026
MO Minimum : Elevators (A) - Hoistways (A)16 No No Bottom floor hoistway door interlock cover is missing, re-install cover 3/25/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Need to test elevator for operation on emergency power. Re-inspection required
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Need to test elevator for operation on emergency power. Re-inspection required 3/25/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Need to test elevator for operation on emergency power. Re-inspection required 7/2/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Need to test elevator for operation on emergency power. Re-inspection required 11/21/2025
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.6.4.20.1 Yes No When the full load car safety test was performed, the car slide was 42". The maximum allowed is 28". Repair or replace car safeties to get proper slide distance. Re-inspection within 30 days required 7/2/2025
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) Yes No Counterweight strikes buffer with car at top floor, has no runby. Hoist ropes need to be shortened. Reinspect within 90 days. 10/14/2021
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) No No Counterweight landing on buffers at top floor, hoist ropes need to be shortened. Re-inspect in 90 days 1206.8 12/28/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No Need to test phase I and II fire service. Re-inspection required 7/2/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No Need to test phase I and II fire service. Re-inspection required 11/21/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No Need to test phase I and II fire service. Re-inspection required 3/25/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display updated Missouri Operating Certificate in machine room 3/25/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display updated Missouri Operating Certificate in machine room 11/21/2025