Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 Bottom floor hoistway door interlock cover is missing, re-install cover
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) x Counterweight strikes buffer with car at top floor, has no runby. Hoist ropes need to be shortened. Reinspect within 90 days. 10/14/2021
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) Counterweight landing on buffers at top floor, hoist ropes need to be shortened. Re-inspect in 90 days 1206.8 12/28/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated Missouri Operating Certificate in machine room
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Need to test phase I and II fire service. Re-inspection required
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Need to test elevator for operation on emergency power. Re-inspection required
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.6.4.20.1 x When the full load car safety test was performed, the car slide was 42". The maximum allowed is 28". Repair or replace car safeties to get proper slide distance. Re-inspection within 30 days required