MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Bottom floor hoistway door interlock cover is missing, re-install cover
|
|
A17.1-1996 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
1001.2(c)(13)
|
x
|
|
Counterweight strikes buffer with car at top floor, has no runby. Hoist ropes need to be shortened. Reinspect within 90 days.
|
10/14/2021
|
A17.1-1996 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
1001.2(c)(13)
|
|
|
Counterweight landing on buffers at top floor, hoist ropes need to be shortened. Re-inspect in 90 days 1206.8
|
12/28/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated Missouri Operating Certificate in machine room
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
Need to test phase I and II fire service. Re-inspection required
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Need to test elevator for operation on emergency power. Re-inspection required
|
|
A17.1-2016 : Elevators
|
2.29 - Car and counterweight safeties
|
8.6.4.20.1
|
x
|
|
When the full load car safety test was performed, the car slide was 42". The maximum allowed is 28". Repair or replace car safeties to get proper slide distance. Re-inspection within 30 days required
|
|