Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm bell and light do not work. 6/25/2020
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) Yes No Suspension cables are below minimum diameter and are rouged, replace suspension cables. Re-inspection required 5/6/2026
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) Yes Yes Suspension cables were written up on 5/8/25 for being undersized and rouged and notice was given to replace within 30 days. Suspension cables were never replaced. Red-tagged and removed from service. Install new suspension cables. Re-inspection required
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No Need to test phase I and II fire service. Re-inspection required 5/6/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display updated Missouri Operating Certificate in machine room 5/6/2026