MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
B(8) Cab lighting shall be guarded to prevent breakage
|
7/13/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.8 Switch Keys
|
x
|
|
Phase I did not initiate when the fireman's emergency service key was turned to the "ON" position. Phase I key switch is broken. Only elevator in building. Re-inspection required within 15 days
|
6/19/2025
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1002.2g (Standby Power Operation)
|
x
|
|
Auxilliary power lowering device is not working, needs repaired. Re-inspection required
|
6/19/2025
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1002.2g (Standby Power Operation)
|
x
|
|
Auxilliary power lowering device is not working, needs repaired. Re-inspection required
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Battery lowering device is not working. Re-inspection required
|
7/10/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
3.26.10
|
x
|
|
Battery lowering device is not working, needs repaired. Re-inspection required
|
6/6/2025
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
|
|
Only 2 of 6 bulbs working
|
9/5/2018
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certificate in machine room
|
6/5/2020
|