Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair the emergency phone as there is no dial tone. 7/8/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair or replace the emergency phone as there is no line voltage. its dead. 8/15/2022
A17.1-1996 : Elevators 1.14 - Ventilation 1001.2(a)(14) Replace the bad exhaust fan in the car top. This ones froze up. 11/1/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair or replace the emergency phone as there is no dial tone. 1/25/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d REmove the existing dead bolt from the machine room door and install a lever latch with a machnical room door lock always locked outside never locked inside. along with a closer as it is to be self closing self latching. 11/1/2020
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) Remove the added dead bolt from the macnine room door. 5/1/2019
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Remove the dead bolt from the machine room door as it is to be a self closing self locking spring type lock always locked outside never locked inside. 9/8/2022
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Remove the mold in the machine room ceiling and replace the drywall thats falling down to provide a min of 1 hour rated assembly 2/16/2022
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Repair the hole cut into the wall to the right of the machine room door back to a 1 hour rating. 2/16/2022
A17.1-1996 : Elevators 2.4 - Machine space 101.1a cover the exposed wood around the new machine room door to provide a min of 1 hour assembly 2/16/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(d) Provide a maintenance control program in the machine room 11/1/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Replace the burnt out pit light. 8/13/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits REplace the burnt out light bulb in the pit 11/1/2020
conversion conversion n/a Repair the non working GFCI on the car top. 5/1/2019
conversion conversion n/a Obtain and display a current state operating certificate in the machine room 5/1/2019
conversion conversion n/a Repair the emergency phone yours does not work 5/1/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room. 11/1/2020