Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Oil Recovery unit the pit does not allow for documenting oil loss as required by the state of Missouri, and A17.1 8.6.5.5.2. Oil recovery units may only be used temporarily if the packing gland is leaking, until the packing gland of the jack can be replaced. After this point , oil recovery unit must be removerd and an oil collection container must be used. 5/11/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (S) - Fire Service (S)1 x Shunt trip device must be manually reset, resetting the fire alarm panel should not reset the elevator and put it back in service after a shunt trip has been activated 10/15/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x x Shunt trip device must be manually reset, resetting the fire alarm panel should not reset the elevator and put it back in service after a shunt trip has been activated 12/26/2019