A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
All Fire service key switches must be keyed the same, As Elevators 1&2 have upgraded to the new required FEO-KI configuration, Cars 3&4 mus be changed to match.
|
10/28/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Oil Recovery unit the pit does not allow for documenting oil loss as required by the state of Missouri, and A17.1 8.6.5.5.2. Oil recovery units may only be used temporarily if the packing gland is leaking, until the packing gland of the jack can be replaced. After this point , oil recovery unit must be removerd and an oil collection container must be used.
|
5/11/2021
|