Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x All fire service key switches in a building must all be keyed alike. As elevators 1&2 have had the key switch upgraded to the now required FEO-K1 Configuration, Elevators 3&4 must be changed to matchiguration 10/28/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Oil Recovery unit the pit does not allow for documenting oil loss as required by the state of Missouri, and A17.1 8.6.5.5.2. Oil recovery units may only be used temporarily if the packing gland is leaking, until the packing gland of the jack can be replaced. After this point , oil recovery unit must be removerd and an oil collection container must be used. 5/11/2021