Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Car fan, on car top has no cover. Fan must have cover 10/16/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.2.3 No No Car fan, on car top has no cover. Provide. 10/16/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 10/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Machine room ventilation unit not working 10/16/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 No No Machine room ventilation unit not working, make so. 10/16/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 10/16/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Provide existing phone to work on emergency power 10/16/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Provide existing phone to work on emergency power (pull 110v) 1/23/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Provide machine room door to be self closing and self locking 10/16/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 No No Provide machine room door to be self closing. 10/16/2025
MO Minimum : Elevators (I) - Pits (I)8 No No Sump pump in the pit is not plugged in. Determine if unit works, if not replace. If electrical issue then repair outlet 10/16/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided Yes No Sump pump in the pit is not plugged in. Determine if unit works, if not replace.if electrical issue then repair outlet. 1/23/2025