Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Based on an installation date of 1966, the hydraulic cylinder is assumed to be of the single bottom type. Proof of a safety bulkhead from the manufacturer is required. If a safety bulkhead cannot be verified, then the installation shall be altered to meet the requirements of A17.1 2016 8.6.5.8. Note: This information has been requested for years, but no documents confirming a double bulkhead exists in the machine room MCP. Failure to comply with this violation may result in the unit being red tagged out of service.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Car top light does not work. Multi-year violation - Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 Pits shall be kept free of dirt and rubbish.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The hall sills at the second and third landing are loose. They shall be properly fastened and the fasteners shall not present a tripping hazard.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car alarm bell shall be operational on auxiliary power.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide a working emergency alarm bell upon removal of 110v. The emergency light was weak as well. 11/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.8 Safety Bulkhead x Provide documentation that can be kept on-site at all times that provides certification that the installed hydraulic jack is a double bottom type. 11/24/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x A sill screw at the top floor landing is protruding and creates a tripping hazard that shall be repaired. (Repeat Violation) 10/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The alarm bell shall operate with 110v source removed. (Repeat Violation) 10/13/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x A sill screw at the top floor landing is protruding and creates a tripping hazard that shall be repaired. (Repeat Violation) 10/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Car top light does not work. Multi-year violation - Re-inspection required 10/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 10/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records There is no MCP in the machine room. 4/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(b) On-Site Maintenance Records (Repair and Replacement Records) Provide documentation that can be kept on-site at all times that provides certification that the installed hydraulic jack is a double bottom type. 4/8/2025
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. 4/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The car top light shall be operational. 4/8/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be obtained and displayed in the elevator machine room. 4/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide a code compliant ABC type fire extinguisher and remove the existing CO2 extinguisher in the machine room. 4/8/2025
MO Minimum : Elevators (I) - Pits (I)1 Remove fluids from the pit, determine source of the leak and repair. 4/8/2025
MO Minimum : Elevators (I) - Pits (I)1 The pit sump pump shall work. 4/8/2025
MO Minimum : Elevators (I) - Pits (I)1 Provide a scavenger bucket in the pit. Connect bucket to head of jack to collect leaking fluids. 4/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Existing car top light is broken and shall be replaced. 4/8/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post the current state operating certificate. 4/8/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits The pit shall be kept clean and dry. Provide means to prevent ground water from entering the pit. 4/8/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 An ABC type fire extinguisher is required in the machine room. Current fire extinguisher is only BC type. 4/8/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 8.6.5.5.2 - Oil leakage collected from the cylinder packing gland shall not exceed 5 gallons before removal. The scavenger container shall be covered and shall not be permitted to overflow. 4/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods A sill screw at the top floor landing is protruding and creates a tripping hazard. Repair as needed. 4/8/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) The car top light shall be operational. 4/8/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(d) On-Site Maintenance Records (Permanent Records) Provide documentation that can be kept on-site at all times that provides certification that the installed hydraulic jack is a double bottom type. 4/8/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate There is no state operating certificate in the machine room. 4/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection A collection container shall be provided in the pit. 4/8/2025