Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide existing battery backup lowering unit to work. 2/14/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Re-inspection of battery lowering rescue unit. Upon removal of mainline power, car automatically returned to bottom landing without the use of a jumper. Provide auxiliary contacts and wiring to prevent elevator from automatically lowering when mainline power is removed. Re-inspection required 5/2/2023
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x Elevator door restrictor does not work, needs repaired. Re-inspection required 12/11/2024