A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.6.4.13.1(l)(Door Restrictor)
|
x
|
|
Elevator door restrictor does not work, needs repaired. Re-inspection required
|
12/11/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide existing battery backup lowering unit to work.
|
2/14/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Re-inspection of battery lowering rescue unit. Upon removal of mainline power, car automatically returned to bottom landing without the use of a jumper. Provide auxiliary contacts and wiring to prevent elevator from automatically lowering when mainline power is removed. Re-inspection required
|
5/2/2023
|