Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x 3 of the suspension ropes are rouged and are stretched. The ropes are to be replaced. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service & Emergency power will be tested at a later date. Re-inspection required
MO Minimum : Elevators (S) - Fire Service (S)1 x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: In phase II operation, the rear car door does not open when activated with the door “open” button pushed. Reinspection is required. 8/23/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the elevator machine room for each elevator 12/11/2023