MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service & Emergency power will be tested at a later date. Re-inspection required
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
3 of the suspension ropes are rouged and are stretched. The ropes are to be replaced. Re-inspection required
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: In phase II operation, the rear car door does not open when activated with the door “open” button pushed. Reinspection is required.
|
8/23/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the elevator machine room for each elevator
|
12/11/2023
|