A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
A fire extinguisher with a current inspection date shall be placed in the machine room
|
|
A17.1-1996 : Elevators
|
2.39 - Low Oil Protection
|
306.16
|
|
|
Door open button shall stay active after low oil timer is active. Reinspect
|
11/19/2019
|
A17.1-1996 : Elevators
|
2.39 - Low Oil Protection
|
306.16
|
|
|
Repair low oil system. Car lowers to the lowest level which is a secure floor after timeout. If door closes, you cannot reopen the door without the security code creating a trap hazard.
|
11/19/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current operating certificate in machine room.
|
4/16/2021
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV not sealed. Perform OSV test on or before next annual inspection.
|
4/16/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall be programmed to answering service that will answer 24/7, this unit has kingsIII that is not being answered
|
5/25/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Auxiliary lowering shall be made operable. Found that there is no switch in the disconnect to let the controller not to run when the power is turned off intentionally.
|
5/25/2023
|