Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 A fire extinguisher with a current inspection date shall be placed in the machine room
A17.1-1996 : Elevators 2.39 - Low Oil Protection 306.16 Door open button shall stay active after low oil timer is active. Reinspect 11/19/2019
A17.1-1996 : Elevators 2.39 - Low Oil Protection 306.16 Repair low oil system. Car lowers to the lowest level which is a secure floor after timeout. If door closes, you cannot reopen the door without the security code creating a trap hazard. 11/19/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room. 4/16/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV not sealed. Perform OSV test on or before next annual inspection. 4/16/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall be programmed to answering service that will answer 24/7, this unit has kingsIII that is not being answered 5/25/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary lowering shall be made operable. Found that there is no switch in the disconnect to let the controller not to run when the power is turned off intentionally. 5/25/2023