A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work.
|
9/11/2018
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
11/6/2020
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/28/2023
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
The pit lighting shall be increased. The lighting shall provide an illumination of not less than 10 foot-candles at the pit floor and at a pit platform, when provided.
|
7/20/2022
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Missing light covers in the car.
|
|
A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
204
|
|
|
204.1b - Missing ceiling tiles in the car.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Water and oil shall not be allowed to accumulate on the pit floor.
|
|
conversion
|
conversion
|
n/a
|
|
|
Repair drop ceiling or protect light bulb in fixtures
|
8/24/2018
|
conversion
|
conversion
|
n/a
|
|
|
Excessive leaking on cylinder packings
|
8/24/2018
|
conversion
|
conversion
|
n/a
|
|
|
Phone shall work
|
8/24/2018
|
conversion
|
conversion
|
n/a
|
|
|
car top shall be kept clean
|
8/24/2018
|
conversion
|
conversion
|
n/a
|
|
|
Pit shall be clean and dry
|
8/24/2018
|