Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MCP needed 6/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door needs to be self-locking. 6/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Scavenger pump not allowed in pit. 6/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 remove non elevator related material from mach room 10/29/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits pit has oil and absorbing mats needed to be cleaned up. leaking jack overflowed bucket needs repack
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals x Recovery pumps not allowed permanently 2/21/2022