Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Top of hoistway smoke damper is in the fully open position, the smoke damper should only open when the smoke detector in the hoistway activates or when the motor fails. Repair top of hoistway smoke damper. A17.1-1990 Rule 100.4
MO Minimum : Elevators (S) - Fire Service (S)1 x Fire service phase 2 instruction sign has the wrong directions on it. Replace sign with the correct one that has directions for "Hold" and "Automatic Return to Recall Floor" 3/28/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors replace broken floor tiles in elevator car (tripping hazzard) 4/9/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) replace pit light bulb and light guard, both were missing at the time of the inspection 4/9/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x the emergency phone did not work, provide working phone line to the elevator controller 3/12/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x replace landing door lock couple rollers at levels G and 2 2/23/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log update firefighters' service operation log 2/23/2021
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Phase I and Phase II firefighters' operation signage/instructions are incorrect 2/23/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) repair the pit light. 2/23/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log The firefighters service test log is not being filled out monthly. 1/3/2022