MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Fire service phase 2 instruction sign has the wrong directions on it. Replace sign with the correct one that has directions for "Hold" and "Automatic Return to Recall Floor"
|
3/28/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)10 Car Floors
|
|
|
replace broken floor tiles in elevator car (tripping hazzard)
|
4/9/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
replace pit light bulb and light guard, both were missing at the time of the inspection
|
4/9/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
the emergency phone did not work, provide working phone line to the elevator controller
|
3/12/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
replace landing door lock couple rollers at levels G and 2
|
2/23/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
update firefighters' service operation log
|
2/23/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Phase I and Phase II firefighters' operation signage/instructions are incorrect
|
2/23/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
repair the pit light.
|
2/23/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
The firefighters service test log is not being filled out monthly.
|
1/3/2022
|