MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
1/17/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Re-inspection required
|
|
|
A17.1-1996 : Elevators
|
2.25 - Traction sheaves
|
1206.1b
|
x
|
|
Sheave groove depths uneven with one another causing unequal rope wear tension and wear. Re-inspection required
|
|