Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 MCP Fire service testing must be properly documented monthly on log sheet.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates COP shall have car number displayed (multiple units onsite).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Replace missing/damaged hoistway door gibs.
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 6/30/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. The phone dials, but no one answers. 5/22/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall work. Repair or replace. 5/22/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. Note: There is a discrepancy regarding if this unit operates on emergency power. Contact is reaching out to electrician and will be providing an update. 5/22/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall work. Repair or replace. (2nd Notice) 6/28/2024