Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 2/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.12 - Car enclosure 8.11.2.1.1(l) Ceiling tile missing in cab.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.4 Protection of Light Bulbs and Tubes Cab ceiling diffuser panel is missing. Replace diffuser panel or install bulb guards on fixture.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) Machine room door strike plate has been removed. Replace
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Observed standing water in the pit, determine if the sump pump is working,
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door is to be self closing and self locking.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Ceiling tile in cab is missing.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Ceiling tile (light diffuser lens) missing from car .
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.