Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space No No Repair hole in machine room wall around sump pump piping 8/5/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self locking & self closing 8/5/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self locking & self closing 8/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces No No Need to repair hole in wall around sump pump piping 8/5/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 8/5/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Provide machine room door to be self closing and self locking. 8/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces No No Seal hole in machine room around sump pipe. 8/5/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency two way phone goes to automated message prompting to dial a key 8/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room expired 2023. Fire extinguisher shall be kept up to date yearly 8/5/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room light is inoperable 8/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces No No Seal hole in machine room around sump pipe.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self locking & self closing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, replace or have serviced
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door has no self-closing, self-locking features. Repair 8/5/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door must be self closing and lockable. 8/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Fill in holes around piping in machine room. 8/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, replace or have serviced 8/5/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone in car unable to provide location, needs to be upgraded to do so. Re-inspection required 8/16/2023