Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space No No Repair hole in machine room wall around sump pump piping 10/21/2025
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space No No Need to repair hole around sump pump piping in machine room wall. 10/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) No No Machine room door has no self-locking features. Repair 10/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Building phone line signal missing from controller to cab, as verified by elevator technician. Restore phone signal and retest. 8/24/2020
conversion conversion conversion - reinspect Yes No Reduce door close pressure to 30# max. 9/17/2018
conversion conversion conversion - reinspect Yes No Repair inoperative emergency phone 9/17/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room expired 2023. Fire extinguisher shall be kept up to date yearly 8/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Yes No Need to reverify relief pressure. Past readings were saying roughly 320 psi and reading for annual is saying 180 psi. Verify if gauge or fitting or valve is bad. Retest 8/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, needs replaced or have serviced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Yes No Relief pressure was only 210 psi. Past readings have been in the 300 psi range. Verify that the elevator will pick the rated load with test weights and record full load working pressure and relief pressure. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Fill holes around piping in machine room. 10/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 9/2/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self locking & self closing 10/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, replace or have serviced 10/21/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone in car is unable to provide location, needs to be upgraded to do so. Re-inspection required 8/17/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self closing & self locking 10/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces No No Need to repair the hole in the wall around the sump pump piping 10/21/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone needs re-programming. It dials a recorded message Re-inspection required 10/21/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self closing & locking 10/21/2025