Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car is unable to provide location, needs to be upgraded to do so. Re-inspection required 8/17/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone needs re-programming. It dials a recorded message Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 9/2/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Fill holes around piping in machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing & locking
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing & self locking
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self locking & self closing
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Building phone line signal missing from controller to cab, as verified by elevator technician. Restore phone signal and retest. 8/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) Machine room door has no self-locking features. Repair
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired, replace or have serviced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces Need to repair the hole in the wall around the sump pump piping
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Need to repair hole around sump pump piping in machine room wall.
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space Repair hole in machine room wall around sump pump piping
conversion conversion conversion - reinspect x Reduce door close pressure to 30# max. 9/17/2018
conversion conversion conversion - reinspect x Repair inoperative emergency phone 9/17/2018