Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Repair inoperative emergency phone 9/17/2018
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space Repair hole in machine room wall around sump pump piping 10/21/2025
conversion conversion conversion - reinspect x Reduce door close pressure to 30# max. 9/17/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Need to reverify relief pressure. Past readings were saying roughly 320 psi and reading for annual is saying 180 psi. Verify if gauge or fitting or valve is bad. Retest
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces Need to repair the hole in the wall around the sump pump piping 10/21/2025
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Need to repair hole around sump pump piping in machine room wall. 10/21/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self locking & self closing 10/21/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing & self locking 10/21/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing & locking 10/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) Machine room door has no self-locking features. Repair 10/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired, replace or have serviced 10/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room expired 2023. Fire extinguisher shall be kept up to date yearly
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Fill holes around piping in machine room. 10/21/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone needs re-programming. It dials a recorded message Re-inspection required 10/21/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car is unable to provide location, needs to be upgraded to do so. Re-inspection required 8/17/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 9/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Building phone line signal missing from controller to cab, as verified by elevator technician. Restore phone signal and retest. 8/24/2020