MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Need a maintenance control program on site posted on controller
|
1/13/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Repair phone in car
|
3/14/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communications/phone inside car not working
|
11/30/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service and document on log in machine room
|
2/9/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Complete 5 yr test within 30 days
|
3/14/2022
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.11.2.1.2(t)
|
x
|
x
|
Tested unintended motion--failed
|
3/25/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.14 - Hoistway clearances
|
2.4
|
|
|
Ring & String not working no reinspection needed
|
1/7/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
2/9/2022
|