Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Complete 5 yr test within 30 days 3/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency communications/phone inside car not working 11/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Repair phone in car 3/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.14 - Hoistway clearances 2.4 Ring & String not working no reinspection needed 1/7/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 2/9/2022
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(t) x x Tested unintended motion--failed 3/25/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need a maintenance control program on site posted on controller 1/13/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room 2/9/2022