Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Sump pump, pumps water into 55 gal. drum in machjine room, not code. Needs to pump water to the outdoors 7/31/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Operating Certificate expired 2019 10/15/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP shall be kept in equipment room, including Testing Procedure(not present) and Fire service testing log, recorded monthly. 10/15/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency/auxiliary lighting shall work with power loss. (REINSPECTION within 30 days) 10/30/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light and bell shall work 10/30/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 6/3/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a maintenance control program on site 6/3/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Provide monthly fire service test & document on log in machine room 6/3/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room 8/11/2022