A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Repair inoperable emergency light. Reinspect.
|
2/11/2021
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Emergency lights shall work.
|
2/11/2021
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate.
|
2/11/2021
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site maintenance control program.
|
11/15/2021
|
A17.1-1996 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
1206.2(c)
|
|
|
Clean oil from car top, fan and ceiling/fixtures.
|
11/15/2021
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean pit.
|
11/15/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Sheave seal worn and leaking, repair as needed. Clean up oil.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Thrust bearing seal worn and leaking, repair as needed.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light housing has rusted away, replace/ repair as needed . Light is laying in pit floor.but works.
|
|
A17.1-1996 : Elevators
|
2.18 - Traction drive machines
|
1001.2(b)(16)
|
x
|
|
Drive sheave seals and worm shaft seals are worn and leaking. Repair as needed.
|
11/15/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
2/25/2021
|