Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not for work properly. Signal present at elevator control panel. 4/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.10 replacement of Hydraulic jack,Plunger,Cylinder,Tanks,and Anticreep Leveling Device x x Failed to hold position during 15 minute standing test. Technician determined that the jack shall be replaced. Unit red tagged.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate shall be displayed in elevator machine room.