MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
Top emergency exit shall be properly secured. The latches are broken.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
x
|
|
Top emergency exit shall be properly secured. The latches are broken. This item requires a re-inspection as it is a repeat violation.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Car top shall be kept clean.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Hoistway doors needs to be cleaned. Door and related hardware are covered in oily lint.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car emergency lighting shall be operational.
|
10/26/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell does not work on battery back-up.
|
1/27/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car emergency alarm bell shall be operational.
|
8/31/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car emergency light shall be operational. (2nd Notice)
|
8/31/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Replace missing fire tabs on hoistway doors (14th floor).
|
10/8/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP and fire service testing logs, which shall be documented monthly.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self-closing and self-locking. Latch does not catch strike-plate.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit needs to be cleaned.
|
8/18/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean and dry. Remove excess debris and repair source of water leak.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Annual inspection not complete. Test car and counterweight buffers.
|
1/27/2022
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency phone not working on battery
|
1/2/2020
|
conversion
|
conversion
|
n/a
|
|
|
Replace hoist cables
|
1/2/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency alarm not working
|
1/2/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
8/18/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|