Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Elevator was not running at the rated speed, could not obtain rated speed to test the car safeties. measured 114 fpm in the down direction car is rated at 200 fpm. reduction in rated speed has not been approved by the AHJ and all the data plates are for a 200 fpm elevator.
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 2 keyswitch in car operating panel does not operate. 11/9/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x Post fire service instructions inside and outside the elevator. 11/9/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x Fire service phase 2 keyswitch is inoperable. 2/8/2019
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x after testing fire service phase 1 and 2, elevator would not answer hall calls but it would run on car calls, repair and retest 12/11/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x did not have the test weights to perform the 5 year weight test, reschedule when test weights are available 12/11/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x elevator safties set with 125% load and could not get elevator off of the safties, 5 year test not completed reinspection is required 2/19/2024