Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair inoperable alarm bell. 7/10/2019
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) Yes No Repair inoperative door restrictor. 2/19/2020
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) No No Replace missing door gibbs 21st and 7th floors 5/12/2021
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) Yes No Replace defective hoist cables due to heavy rouge and diameter reduction by 1/20/20 2/19/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal Yes No Fire recall buzzer inoperative. 4/23/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 4/23/2021
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code No No Replamp machine room lighting fixtures above machines. 5/12/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO state operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vison plate over it. 12/31/2024
A17.1-1996 : Elevators 3.27 - Crosshead data plate 212.2 No No Suspension ropes shall have proper data tag(s)
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be kept clean. Remove excess debris
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.11.2.1.2(ff) Yes Yes Govenor test failed, Red tagged elevator 1/27/2022
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Yes No Upper hoistway door hanger safety retainers are defeated/turned down on almost all doors. Shall be corrected. (Previously Cited Violation)
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No Counterweight runby, 1.5", does not meet Code Requirements. Shorten cables
A17.1-2016 : Elevators 1.16 - Rated load, platform area, and data plate 2.16.5 No No COP shall have car number displayed, 0.5" lettering.
A17.1-2016 : Elevators 1.12 - Car enclosure 8.11.2.1.1(l) No No Iron on cab walls needs to be secured 1/27/2022
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) No No Fire tabs on door hangers 1/27/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No Dust covers in machine room 1/27/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No Exposed live wiring on brake switches 1/27/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Need light above controller 1/27/2022