MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2022.
|
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
207
|
|
|
There is no car capacity plate inside the elevator stating the rated load of the car, as required.
|
|
A17.1-1996 : Elevators
|
1.4 - Sills and car floor
|
1001.2(a)(4)
|
|
|
204.2b Flooring has been added that interferes with the opening of the car operating panel denying access to the emergency battery for the alarm bell and emergency lighting. Readjust flooring or car operating panel.
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Re-inspection required
|
12/10/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Bell not working.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required.
|
11/12/2024
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
112.2a
|
|
|
Elevator will run with car gate open 3 1/2". Maximum opening is 2". Reinspect within 30 days.
|
11/5/2020
|
A17.1-1996 : Elevators
|
1.8 - Door closing force
|
1001.2(a)(8)
|
x
|
|
Door force exceeds 30#.
|
9/1/2022
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV installed and not sealed. Perform OSV test on or before next annual inspection.
|
4/28/2021
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Expired
|
9/1/2022
|
A17.1-1996 : Elevators
|
3.19 - Guide rails fastening and equipment
|
1001.2(c)(25)
|
|
|
200.7b(1)(c) The guide rail fishplate is missing a bolt the right side looking in the hoistway between the 1st and 2nd landing.
|
|
A17.1-1996 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
1206.2(c)
|
|
|
Clean elevator car top.
|
11/5/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Provide working pit light.
|
9/1/2022
|
A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(4)
|
|
|
Packing (left jack) worn and leaking.
|
9/1/2022
|