Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Car directional arrows, missing lens-provide. 3/13/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone in car does not provide 2 way communication, needs repaired. Re-inspection required 3/13/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Provide missing directional arrow lens 3/13/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair emergency phone. 7/8/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working. 10/30/2019
A17.1-1996 : Elevators 1.7 - Car door or gate 1001.2(a)(7) No No The gap between elevator cab and car door are over 3/8" when the door is in the closed position. 9/22/2020
A17.1-1996 : Elevators 1.7 - Car door or gate 204.4 No No There is an 1 1/8" gap between the cop and the car door. Needs to be fixed. Reinspect. 7/25/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit is not working properly at the time of inspection.
A17.1-1996 : Elevators 3.13 - Windows, projections, recesses, and setbacks 1001.2(c)(19) No No Toe guard is hitting the landing sill guard in elevator pit. 9/22/2020
A17.1-1996 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 1206.2(c) No No Clean elevator car top. 9/22/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a Yes No Light needs to work in the pit. 7/8/2019
conversion conversion n/a No No Post Mo State certificate in machine room 7/25/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate in machine room. 7/25/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate in machine room. 7/25/2019