Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire” the missing. Install signage that conforms to the building code this elevator was installed to conform to.
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to conform to.
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x Machine room door shall be self-closing and self-locking. 5/28/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Disconnect breaker jams, not allowing for proper opening of mainline circuit. 5/28/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Disconnects does not have 36" workspace clearance to nearest object (air handler). 5/28/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power must be tested. 5/28/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power must be tested.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x When testing the ADA telephone with the 110V disconnect in the machine room in the “off” position, the device failed to operate, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 5/16/2024