Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Unit shall have a clean-down performed. 8/16/2022
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing Incomplete: Only performance index testing and handrail condition tested. 7/31/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.1 Escalator Handrails x Handrails will be free of major cracks and pinch points. Replace left handrail. Violation originally cited in 2024 still not corrected. 45 days to correct at which point unit will be red tagged until corrected.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.3 Step/Skirt Performance Index x Step Index Performance Testing shall be performed and confirmed compliant. Graph to be provided.
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it. 11/24/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.3 - Handrails 6.1.3.4 (Hand rails) (Re-Inspection) x Handrails will be free of major cracks and pinch-points. Replace left handrail. 7/31/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Certificate A current MO State operating certificate shall be obtained and displayed. 11/24/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.3 - Handrails 6.1.3.4 (Hand rails) (Re-Inspection) x Handrails will be free of major cracks and pinch-points. Replace left handrail. - Violation not corrected as of 7/31/24 re-inspection to complete testing. 7/7/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.19 - Maintenance records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided. (This item is for notification purposes for future violation in 2022) 8/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Certificate A current MO State operating certificate shall be obtained and displayed. 8/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.5 - Lighting 8.6.11.5(i) Demarcation Lighting (Re-Inspect) x Upper & lower step demarcation lighting not working. 7/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.17 - Step/skirt clearances, panels, and performance index 8.6.8.3 Step/Skirt Performance Index x Performance index testing graphs, including loaded gap, CoF, Index, etc. to be sent to inspector for verification of results. Note: Step indexing machine broke after completion of this testing. 7/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.1 Provide clean down of unit. 8/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.12 - Steps, step chains, and trusses 8.11.4.2.12 Observed numerous damaged and broken step demarcation indicators that shall be repaired or replaced as needed. 8/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.11.4.2.1 (Re-Inspection) Existing upper and lower demarcation lights shall work. 8/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.5 - Lighting 8.6.11.5(i) Demarcation Lighting (Re-Inspect) x The demarcation lights shall be operational. 9/20/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.9 - Steps and upthrust device 8.6.8.6.1 Steps with broken treads shall be repaired or replaced x x Replace the broken step tread. 9/20/2021