Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.1 Provide clean down of unit. 8/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.12 - Steps, step chains, and trusses 8.11.4.2.12 Observed numerous damaged and broken step demarcation indicators that shall be repaired or replaced as needed. 8/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.11.4.2.1 (Re-Inspection) Existing upper and lower demarcation lights shall work. 8/16/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Unit shall have a clean-down performed. 8/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.19 - Maintenance records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided. (This item is for notification purposes for future violation in 2022) 8/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Certificate A current MO State operating certificate shall be obtained and displayed. 8/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Certificate A current MO State operating certificate shall be obtained and displayed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.3 - Handrails 6.1.3.4 (Hand rails) (Re-Inspection) x Handrails will be free of major cracks and pinch-points. Replace left handrail. - Violation not corrected as of 7/31/24 re-inspection to complete testing.
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.5 - Lighting 8.6.11.5(i) Demarcation Lighting (Re-Inspect) x Upper & lower step demarcation lighting not working. 7/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.17 - Step/skirt clearances, panels, and performance index 8.6.8.3 Step/Skirt Performance Index x Performance index testing graphs, including loaded gap, CoF, Index, etc. to be sent to inspector for verification of results. Note: Step indexing machine broke after completion of this testing. 7/19/2024
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing Incomplete: Only performance index testing and handrail condition tested. 7/31/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.3 - Handrails 6.1.3.4 (Hand rails) (Re-Inspection) x Handrails will be free of major cracks and pinch-points. Replace left handrail. 7/31/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.5 - Lighting 8.6.11.5(i) Demarcation Lighting (Re-Inspect) x The demarcation lights shall be operational. 9/20/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.9 - Steps and upthrust device 8.6.8.6.1 Steps with broken treads shall be repaired or replaced x x Replace the broken step tread. 9/20/2021