Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Emergency communications loss monitor shall work. 3/20/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x FAID testing failed. 3/20/2024
A17.1-2016 : Elevators 4.5 - Access to Hoistway 2.12.7 x Adjust hoistway access limits. 3/20/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Disconnects: label feeder location. 3/20/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power shall be tested. Test to be performed when Car 1 is ready for acceptance. 12/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Car button braille is mislabeled. 3/20/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Major alteration acceptance: test incomplete due to shutdown. Still need to test: hoistway, cartop, doors, gates, restrictor, light, bell, phone, EP. 3/20/2024